China · Pressurized water reactor

Sanmen.

4 AP1000 units at Sanmen, beside the AP1000 plant concept. The 3D model shows how the AP1000 design works; it is not Sanmen's actual layout.

Back to the globe at Sanmen
Close view of the illustrative AP1000 concept: a steel containment cut open inside a concrete shield building, with a ring-shaped cooling-water tank on the roof, and inside it two tall steam generators with four pumps hanging under them, the reactor vessel with its core and drive mechanisms, and a pressurizer, joined by red hot legs and blue cold legs.DESIGN CONCEPT · NOT A SIMULATION

Reference still · interactive view loads when available

Named design · AP1000

The AP1000 plant concept.

The AP1000 design’s concept, not Sanmen. The model shows how an AP1000 plant works, drawn from the design’s public description, in the generic layout every design in the plant library shares: the reactor island, a turbine hall, air-cooled condensers and a grid connection. It does not show Sanmen's buildings, number of units, cooling or equipment.

The concept follows the AP1000 as certified. China’s CAP1000 units are a local standardization of it, built after the technology was transferred over the first four Chinese AP1000s, so their equipment and details may differ from what is drawn. Everything here, containment and cooling tank included, is drawn at 0.26 of full size, and the shared building frame stands in for the auxiliary and turbine buildings.

A two-loop pressurized water reactor of about 1,100 MWe. Water at 15.4 MPa carries heat from a 157-assembly core through two hot legs to two vertical U-tube steam generators, and four canned-motor pumps, hung upside down from the generators’ channel heads, send it back through four cold legs. Its safety systems need no pumps or AC power: after an accident, water drains from a tank on the shield building roof over the steel containment, and rising air carries the heat away.

Fuel
Uranium dioxide
Reaction
Splitting heavy nuclei
Energy transfer
Two-loop pressurized water primary circuit

The loop, generator, pump and assembly counts, the vessel, generator, pressurizer and containment envelopes and the pipe sizes follow the IAEA status report and the IAEA’s 2004 technical data. The whole island, containment and tank included, is drawn at one scale, 0.26 of full size, so it fits the bay; elevations, loop spacing, pump proportions, the shield building, roof and tank, valves and the steam and feed headers are illustrative. The tank roof is left off so the water shows, the water film is drawn as if the system had started, and the containment wall is drawn about twice its 44 mm thickness.

Concept source: IAEA ARIS · Status report: AP 1000 (2024). Procedural geometry drawn for teaching: source anchors are identified in the component records; other dimensions and placement are illustrative. No physics results are computed.

Units the source data files as AP-1000 and CAP1000 open this concept. Other PWR units open the family’s pressurized water reactor reference concept.

Spotter’s guide · PWR

Pressurized water reactor

Water held at around 155 bar stays liquid as it carries heat from the core to steam generators, where a second loop boils. The most common reactor on Earth.

VVER · AP1000 · EPR · APR-1400 · Hualong One

Inside the reactor · AP1000

The AP1000 by its published numbers.

Each figure is the design’s own, as its source publishes it, with the page it is on. They describe the design, not any station: built units may be uprated, and the station’s own capacities are in its unit table. Nothing here is computed.

157 fuel assemblies on a square lattice (IAEA ARIS status report, Table 2, Number of Fuel Units, p. 6). Drawn to the published count and packed to a circle: the real core outline steps differently at its edge, and no loading pattern, fuel batch or control position is shown.
Power
Thermal power3,400 MWtIAEA ARIS status report, Table 2, Single Core Thermal Power, p. 6
Gross electric output1,200 MWeIAEA ARIS status report, §1 Overview, p. 1
Net electric output1,100 MWeIAEA ARIS status report, §1 Overview, p. 1
Turbine speed1,800 (1,500 for 50 Hz) rpmIAEA ARIS status report, §5.5 Secondary Side, p. 21
Core
Fuel assemblies157IAEA ARIS status report, Table 2, Number of Fuel Units, p. 6
Assembly rod array17×17, squareIAEA ARIS status report, Table 1, Fuel Lattice Shape and Rods per Assembly, p. 3
Fuel rods per assembly264IAEA-TECDOC-1391 (2004), §4.10.8 Technical data, Reactor core, printed p. 302
Active core height4.267 mIAEA ARIS status report, Table 2, Active Core Height, p. 9
Equivalent core diameter3.04 mIAEA ARIS status report, Table 2, Equivalent Core Diameter, p. 9
Control rods69 (53 black, 16 gray)IAEA-TECDOC-1391 (2004), §4.10.8 Technical data, Reactor core, printed p. 302
Uranium loading (initial core)~87,000 kgUIAEA ARIS status report, Table 2, Total Fissile Loading, p. 6
Enrichment, average/maximum (18-month equilibrium reload)4.54/4.95 %IAEA ARIS status report, Table 2, Enrichment, p. 6
Refueling cycle18 (12 or 24 also possible) monthsIAEA ARIS status report, Table 2, Refuelling Cycle, p. 6
Reactor coolant system
Coolant loops2 (each one hot leg, two cold legs)IAEA ARIS status report, Table 1, NSSS Layout, p. 3; §5.1, p. 15
Steam generators2, vertical U-tubeIAEA ARIS status report, Table 2, Steam Generator Design, p. 6; §5.1, p. 15
Reactor coolant pumps4, canned motor (sealless), two on each steam generatorIAEA ARIS status report, Table 1, Primary Circulation, p. 3; §5.1, p. 15; p. 22
Primary pressure15.4 MPaIAEA ARIS status report, Table 2, NSSS Operating Pressure (primary side), p. 5
Primary coolant flow15,120 kg/sIAEA ARIS status report, Table 2, Nominal Coolant Flow Rate (primary), p. 5
Core inlet temperature280.7 °CIAEA ARIS status report, Table 2, Core Inlet Coolant Temperature, p. 5
Core outlet temperature321.1 °CIAEA ARIS status report, Table 2, Core Outlet Coolant Temperature, p. 5
Steam and feedwater
Steam pressure5.76 MPaIAEA ARIS status report, Table 2, System Steam Pressure, p. 9
Steam temperature272.8 °CIAEA ARIS status report, Table 2, System Steam Temperature, p. 9
Steam flow1,889 kg/sIAEA ARIS status report, Table 2, System Steam Flow Rate, p. 9
Feedwater temperature226.7 °CIAEA ARIS status report, Table 2, System Feedwater Temperature, p. 9
Vessel and containment
Vessel inside diameter (core region)~4.039 mIAEA ARIS status report, §5.1 Primary Circuit, p. 15
Vessel length~12.0 mIAEA ARIS status report, §5.1 Primary Circuit, p. 15
Vessel shell wall203 mmIAEA-TECDOC-1391 (2004), §4.10.8 Technical data, Reactor pressure vessel, printed p. 302
ContainmentFree-standing steel vessel, 39.624 m diameter, 65.634 m high, 44.45 mm wall, cooled passivelyIAEA ARIS status report, §5.6 Containment/Confinement, p. 21; §5.4, p. 20
Design life60 yearsIAEA ARIS status report, Table 2, Design Life, p. 4

Sources: IAEA ARIS status report; IAEA-TECDOC-1391 (2004). Page numbers refer to the copies read on 2026-11-07; the IAEA builds its status reports when they are downloaded, so its pagination can shift.

From reactor to grid · AP1000

Where the AP1000’s heat goes.

One unit at its design rating, from the published figures above. Most of the reactor’s heat leaves through the condenser to the cooling water or air; the rest becomes electricity, some of which runs the plant itself. A figure marked “derived” is plain arithmetic on published ones; nothing is simulated.

Used in the plant
100 MWeDerived: 1,200 MWe gross less 1,100 MWe net
Heat rejected through the condenser
2,200 MWtDerived: 3,400 MWt of reactor heat less 1,200 MWe gross
Net efficiency
about 32.4 %Derived: 1,100 MWe net of 3,400 MWt
  1. 01 Heat source
  2. 02 Steam
  3. 03 Turbine and generator
    Turbine speed
    1,800 (1,500 for 50 Hz) rpmIAEA ARIS status report, §5.5 Secondary Side, p. 21
  4. 04 Cooling and return
    Heat rejected
    2,200 MWtDerived
  5. 05 Grid connection
    Used in the plant
    100 MWeDerived
    Net efficiency
    about 32.4 %Derived

Sanmen’s 2 operating AP1000 units at design rating

Together they would take 6,800 MWt of heat from their reactors and reject 4,400 MWt to their cooling. Their own published net capacities add to 2,314 MWe.

Derived: 2 units × 3,400 MWt; 2 units × 2,200 MWt. Built units may be uprated or run below rating, so these are the design’s figures scaled by the unit count, not the station’s operating data.

The whole station · Sanmen

Sanmen as one power plant.

Every unit on the site, from the atlas’s unit records: each reactor drives its own generator, which feeds the station’s switchyard and the grid. This is a schematic of how the units connect, not the station’s layout; the atlas records no buildings, cooling, switchyard arrangement or grid voltage.

Sanmen-1: AP1000, operating, 1,157 MWe net, 3,400 MWt at design ratingSanmen-1AP10003,400 MWtG1,157 MWeSanmen-2: AP1000, operating, 1,157 MWe net, 3,400 MWt at design ratingSanmen-2AP10003,400 MWtG1,157 MWeSanmen-3: AP1000, under construction, 1,163 MWe net, 3,400 MWt at design ratingSanmen-3AP10003,400 MWtG1,163 MWeBuildingSanmen-4: AP1000, under construction, 1,163 MWe net, 3,400 MWt at design ratingSanmen-4AP10003,400 MWtG1,163 MWeBuildingSwitchyardGridSanmen-1: AP1000, operating, 1,157 MWe net, 3,400 MWt at design ratingSanmen-1AP1000 · 1,157 MWeGSanmen-2: AP1000, operating, 1,157 MWe net, 3,400 MWt at design ratingSanmen-2AP1000 · 1,157 MWeGSanmen-3: AP1000, under construction, 1,163 MWe net, 3,400 MWt at design ratingSanmen-3AP1000 · 1,163 MWe · BuildingGSanmen-4: AP1000, under construction, 1,163 MWe net, 3,400 MWt at design ratingSanmen-4AP1000 · 1,163 MWe · BuildingGGrid
  • Operating · 2
  • Under construction · 2
  • On this page
Operating
2 units · 2,314 MWe netPublished net capacities, from the unit table
Being built or planned
2 units · 2,326 MWe net
Heat at design rating
6,800 MWt in, 4,400 MWt rejectedDerived: 2 operating units of a named design, each at its design’s published rating
Plant concepts here
AP1000 (4)